PRODUCTS SUMMARY

single phase transformers 

control

ITAlia (50-3000VA)

EUR multitap (50-3000VA)

ET (50-3000VA)

MC (4000-20000VA)

isolation and safety

TEcna (50-2000VA)

GT (50-2000VA) UL APPROVED

ALI (50-1000VA) LIGHTING 12V

TMIC (3000-25000VA)

TMI64 (3000-25000VA-medical)

specific use

ALX 200-500VA) ip55 class II

AL (50-1500VA) HALOGEN LAMPS

three phase transformers

power

TTP (1-100kVA)

isolation and safety

TTI (1-40kVA)

autotransfomers

SB 110/220V reversible

ATM (single ph. 0,1-5kVA)

KVA (three ph. 1-500kVA)

ATTP (three ph. 1-300kVA)

ATTP1 (three ph. +box 1-300kVA)

ATV (motor starting  7-220kW)

---------

metal enclosures

--------

voltage stabilisers

AVR voltage regulators

SEN single ph. electronic 

SED single ph. electronic

RA 1ph. servo motor 0,5-3kVA

Line conditioners for HI-FI 1.5-2.5k

RB single ph. electromechanical

R25 single ph. ±25% input

RTC three ph. electromechanical

RTC 220V three ph. NO NEUTRAL

RTI three ph.line conditioners

RTG three ph. electromechanical

uninterruptible power supplies

EB Unin.power supplies (UPS) to 2kVA

GEI sine wave ups to 3kVA

GET sine wave on-line ups to 10kVA

other products

frequency converters 60-50Hz

Hospital earth leakage control

230V-110V ADAPTERS

Motor Guard (motor protection)

versione italiana

go to our UK Web site:
www.ideomat.co.uk

copyright 2001-2004 by:

web factory

   

INDUSTRIAL CONTROL TRANSFORMERS GT range UL (C-UL)

POWER INPUT OUTPUT FREQUENCY STANDARDS
DA 50 A 2000VA su richiesta
da 220V fino a 600V
su richiesta
da 12V fino a 600V
50/60 Hz

EN61558-2-4 / 2-6

UL 506

CSA 22.2

 Open type, class I
 Protection IP00
 Isolation (temperature) class A (At max 45°C) up to 250VA
 Isolation (temperature) class F (At max 45°C) from 300VA
 Separate copper windings cl. F-H
 certified isolated system 420-155
 Resin impregnated and tropicalised
 Earthed copper screen between pri and sec. windings on terminal
   blocks

 DIN50022 rail fixing accessory up to 500VA included
 Universal fixing centres
 Double secondary voltage with full rating intermediate voltage on
   request
 Links for secondary parallel-series connection
 IP20 terminal blocks with access on two sides



LISTED

FILE E3210


INF. 50V


power part no. dimensions mm. DWG weight box
VA A B C D E F kg. code
50 GT19009.. 85 68 82 72 54 5 A 1.4 MB01
75 GT19014.. 85 68 82 72 54 5 A 1.7 MB01
100 GT19029.. 85 76 82 72 64 5 A 2.1 MB01
160 GT19051.. 97 82 92 80 64 6 A 2.9 MB02
250 GT19069.. 97 102 92 80 84 6 A 3.7 MB02
400 GT19099.. 121 105 112 100 92 6 A 6.2 MB03
500 GT19119.. 121 115 112 100 102 6 A 7.2 MB03
630 GT19145.. 154 128 148 125 103 8 B 8.4 MB04
800 GT19171.. 154 138 148 125 113 8 B 8.9 MB04
1000 GT19179.. 154 138 148 125 113 8 B 10.8 MB04
1500 GT19199.. 184 170 173 150 115 8 B 18.0 MB05
2000 GT19219.. 184 180 173 150 125 8 B 19.6 MB05

complete part nos. to be assigned at the order according to primary and secondary voltages

A

B
power losses inrush VA as a function of cos-phi short circuit regulation
VA W 0.9 0.8 0.7 0.6 0.5 0.4 voltage % %
50 8 60 70 75 80 85 100 16.2 14.1
75 12 95 105 120 140 160 200 11.3 10.2
100 14 140 160 170 190 230 270 9.2 7.6
150 16 210 280 360 410 490 560 6.3 6.4
200 18 300 370 440 520 590 690 5.2 5.6
300 30 380 460 545 630 745 830 4.6 4.4
400 34 510 620 730 820 935 1020 4.4 4.4
500 38 640 780 920 1030 1180 1290 4.2 4.4