UNINTERRUPTIBLE POWER SUPPLIES GET RANGE |
|
from 1kVA
to 10kVA |
|
 |
~ Microprocessor control
guarantees high reliability
~ PWM Technology with IGBTs.
~ Communication Ports Selectable : Smart RS-232 and Intelligent slot for
AS-400, and SNMP card
.~ Equipped with the comprehensive self-protection design
~ Maintenance Bypass Switch, DSP technology application, and Two-step
Battery Charging Mode available
~ Intelligent SNMP slot to allow communication among various operation
systems and remote monitoring of the UPS
~ Audible Alarm Mute
~ Cold Start Function
~ Auto self-testing System while turning on the UPS
~ External battery connections for extended backup time available for ET
(S) models
 |
| MODEL |
GET01 |
GET02 |
GET03 |
GET06 |
GET10 |
| POWER |
1000VA/700W |
2000VA/1400W |
3000VA/2100W |
6000VA/4200W |
10000VA/7000W |
| Vai
- computer load |
1500Vai |
3000Vai |
4000Vai |
8000Vai |
15000Vai |
| INPUT |
| rated
acceptable input voltage |
from
80 to 300 Vac |
from
176 to 276 Vac |
| min.
transfer line voltage |
from
160Vac to 118Vac according to load % |
176
± 1% Vac |
| max. transfer
line voltage |
300Vac |
276
± 1% Vac |
| frequency |
da
46 a 54Hz |
da 46 a 55Hz |
| connections |
lead + plug |
terminal blocks |
| BATTERIES |
| No. of
batteries |
3 |
8 |
8 |
20 |
40 |
| rated
voltage |
12V |
12V |
12V |
12V |
24V |
| ampere |
7Ah |
7Ah |
7Ah |
7Ah |
7Ah |
| max
authonomy PF=1,0/0,7/0,5 |
5'/9'/14' |
9'/15'/25' |
5'/9'/15' |
8'/13'/17' |
8'/13'/17' |
| charging
current |
1A |
1A |
1A |
1,5A |
2A |
| charging
voltage |
41.1Vdc
± 0.6V |
110Vdc
± 0.4V |
274Vdc
± 5% |
| recharge
time |
5h al 90% |
5h al 90% |
5h al 90% |
8h al 90% |
| OUTPUT |
| voltage |
220Vac
/ 230Vac / 240Vac |
| output
accuracy |
±
2% |
±3% |
| wave form |
sine wave |
| transfer
time AC/DC |
zero |
| inverter
frequency |
50
± 0.2 Hz |
| PROTECTIONS |
| LED SIGNALS |
battery level / load level / Battery mode / AC mode / Bypass mode /
Fault |
| inverter mode |
sound alarm every 4" |
| low battery |
sound alarm every 1" |
| overload |
sound alarm every 0.5" |
| fault |
countinous sound alarm |
| OTHER
DATA |
| acceptable
humidity |
20-90%
(0°C - 40°C) |
| audible
noise level |
<50
dBA a 1 mt. |
| dimensions
mm. (WxDxH) |
145x400x220 |
192x460x340 |
192x460x340 |
260x570x517 |
340x640x980 |
| net weight kg |
13 |
32 |
33 |
84 |
163 |
|